Commercial Kitchen Hood Sizes: Length, Overhang & CFM Chart

By Equipment Specialist Team Last reviewed

Commercial hoods aren't sold in a few fixed sizes. They're built to length, in feet, to cover the cook line. The International Mechanical Code (2015 IMC Section 507.4.1) requires a canopy hood's inside lower edge to extend at least 6 inches past the cooking surface on every open side. The front lower lip can be no more than 4 feet above the cooking surface. So a wall hood with both ends open must be at least 12 inches longer than the cook line. A 10-foot line needs a hood of at least 11 feet. You need a Type I (grease) hood over medium-, heavy- and extra-heavy-duty appliances. Type II hoods go over dishwashers and appliances that give off heat or moisture but no grease or smoke.

RuleRequirementIMC 2015 section
Canopy overhang (Type I and Type II)Inside lower edge must extend at least 6 in. (152 mm) past the edge of the appliance's top surface on all open sides507.4.1
Canopy heightVertical distance from the hood's front lower lip to the cooking surface may not exceed 4 ft (1219 mm)507.4.1
Canopy overhang exceptionHood may be flush with the outer edge of the cooking surface where a noncombustible wall or panel closes that side507.4.1 Exception
Non-canopy (backshelf/proximity) hoodsNo more than 3 ft (914 mm) above the cooking surface; edge set back no more than 1 ft (305 mm) from the edge of the cooking surface507.4.2
Where Type I is requiredWhere appliances produce grease or smoke, and over all medium-, heavy- and extra-heavy-duty cooking appliances507.2
Where Type II is requiredOver dishwashers and appliances that produce heat or moisture but not grease or smoke (unless that load is handled by the HVAC design or a separate removal system), and over appliances that produce combustion products but not grease or smoke507.3
Type I clearance to combustiblesAt least 18 in. (457 mm). Exception: none required from gypsum or 1/2-in. cementitious wallboard on noncombustible structure when faced with smooth, cleanable, noncombustible material extending at least 18 in. in all directions from the hood507.2.6
Extra-heavy-duty hoodsMay not also cover heavy-, medium- or light-duty appliances; must discharge to an independent exhaust system507.2.2
Exhaust outletsEach outlet may serve no more than a 12-ft (3658 mm) section of hood507.1.5
Grease filter height above cooking surface (minimum)0.5 ft without exposed flame; 2 ft with exposed flame and burners; 3.5 ft for exposed charcoal and charbroil-typeTable 507.2.8
Type I materialSteel at least 0.0466 in. (No. 18 gage) or stainless steel at least 0.0335 in. (No. 20 MSG)507.2.3
Code rules that set hood size and placement (2015 International Mechanical Code text, verified; confirm the edition your jurisdiction has adopted) Sources: bellevuewa.gov.
Appliance dutyWall-mounted canopySingle island canopyDouble island canopy (per side)Backshelf/pass-overEyebrow
Extra-heavy-duty550700550Not allowedNot allowed
Heavy-duty400600400400Not allowed
Medium-duty300500300300250
Light-duty200400250250250
Dishwashing (Type II)100 cfm/ft of hood length (507.5.5)————
Minimum net exhaust in CFM per linear foot of hood, for unlisted hoods sized by the code (IMC 2015 Section 507.5). Listed hoods may use the CFM/ft on their label (507.2.1). Sources: bellevuewa.gov.
ModelType / styleListed cooking-surface tempsHung height (bottom edge above cooking surface)Min. exhaust CFM/ft (single hood; back-to-back in parentheses)Notes
CaptiveAire ND-2Type I wall canopy, exhaust only450°F, 600°F, 700°F33–48 in. with lights; 11.5–48 in. without lights150 / 200 / 250 at 450 / 600 / 700°F (300 / 400 / 500)Standard built-in 3 in. rear standoff; extra hanging angles on hoods longer than 12 ft; a 4-ft hood can run at 150 CFM/ft (600 CFM total); ETL listed, complies with UL710
CaptiveAire SND-2Type I sloped wall canopy for low ceilings, exhaust only400°F, 600°F33–48 in. with lights; 11.5–48 in. without lights228 / 294 at 400 / 600°F (456 / 588)Sloped canopy built for low ceiling heights
CaptiveAire ND-2WIType I single-island canopy450°F, 600°F, 700°FNot stated on product page269 / 300 / 350 at 450 / 600 / 700°FFor cooking lines with no wall behind them, or display cooking
CaptiveAire VHBHeat and condensate vent hoodNot applicableNot stated on catalog pageSee manufacturer labelFor heat/moisture loads, the kind of application the IMC assigns to Type II hoods; ETL listed, complies with UL710
Example hood models from CaptiveAire (manufacturer data). Lengths are built in feet to fit the line, so these rows show each model's type and mounting data rather than fixed sizes. Sources: captiveaire.com, captiveaire.com, captiveaire.com, captiveaire.com.

How to choose the right size

  • Hood length: measure the cook line from the outside edge of the first appliance to the outside edge of the last, then add 6 in. for each open end (IMC 2015 507.4.1). A 120-in. (10-ft) line with both ends open needs at least 132 in. (11 ft) of hood. With a noncombustible wall or end panel on one side, that side may be flush, so the same line needs at least 126 in.
  • Hood depth: the inside lower edge must also extend at least 6 in. past the front of the appliances. So the depth from the wall has to cover any rear standoff (CaptiveAire builds in 3 in. on the ND-2), the gap between wall and appliance, the appliance depth, and 6 in. of front overhang. CaptiveAire's manual says its ETL zero-clearance installation requires appliances at least 6 in. from the rear wall and at least 24 in. below the hood's bottom edge. Measure your actual appliances, and confirm with the manufacturer's submittal drawing.
  • Mounting height: the front lip can be no more than 4 ft above the cooking surface (IMC 507.4.1). CaptiveAire hangs the ND-2 and SND-2 with the bottom edge 33–48 in. above the cooking surface (with lights). Its installation manual says canopy hoods are typically hung with the front lower edge 6'-6" to 7'-0" above the finished floor. Check the hood's nameplate and your local authority.
  • Airflow sets fan and makeup air size: multiply the hood length by CFM per foot. An unlisted 11-ft wall canopy over heavy-duty appliances needs at least 11 × 400 = 4,400 CFM (IMC 507.5.2). A listed hood can use its labeled rate. The CaptiveAire ND-2 lists 200 CFM/ft at 600°F, so an 11-ft ND-2 at that rating needs 2,200 CFM. The code also requires makeup air approximately equal to the exhaust (IMC 508.1).
  • Mixed lines: when one hood covers a mix of heavy-, medium- and light-duty appliances, the IMC sizes the whole hood's exhaust for the heaviest-duty appliance under it (507.5). Extra-heavy-duty appliances, which the IMC defines as those using open-flame combustion of solid fuel, can't share a hood with lighter appliances and need an independent exhaust system (507.2.2).
  • Long lines and ceilings: each exhaust outlet may serve no more than a 12-ft section of hood (IMC 507.1.5). Type I hoods need 18 in. of clearance to combustibles unless the 507.2.6 wallboard exception applies or a listed method is used. Check ceiling height, ductwork, and the structure that will carry the hood before you order.

Not sure which size fits?

Send your space dimensions, menu and volume. A specialist will recommend sizes across brands and quote them with freight included. Or call (732) 479-6550.

Get a Free Quote Call (732) 479-6550

Frequently asked questions

How much bigger than the cooking equipment does a hood need to be?

Under IMC 2015 Section 507.4.1, a canopy hood's inside lower edge must extend at least 6 inches past the cooking surface on every open side, front included. A wall hood with both ends open is therefore at least 12 inches longer than the line. A side closed by a noncombustible wall or panel may be flush. Your local code edition and amendments govern, so confirm with your authority having jurisdiction (AHJ).

What is the difference between a Type I and Type II hood?

A Type I hood is a grease hood. The IMC requires it where appliances produce grease or smoke, and over all medium-, heavy- and extra-heavy-duty cooking appliances. It needs UL 1046 listed grease filters (507.2.8), continuous liquid-tight external welds or brazes (507.2.5) and, per IMC 509.1, an automatic fire suppression system. A Type II hood goes over dishwashers and appliances that produce heat, moisture or combustion products but no grease or smoke (507.3).

How high should a commercial hood be mounted?

The IMC limits the front lower lip of a canopy hood to 4 feet above the cooking surface. Manufacturers list their own ranges. CaptiveAire hangs the ND-2 with its bottom edge 33–48 inches above the cooking surface (with lights), and its installation manual gives a typical front-edge height of 6'-6" to 7'-0" above the finished floor. Always check the hood's nameplate.

How many CFM does my hood need?

For unlisted hoods, the IMC sets minimums per linear foot by hood style and appliance duty. Wall canopies need 200 CFM/ft (light-duty), 300 (medium), 400 (heavy) and 550 (extra-heavy). Listed hoods may run at their labeled rate. The CaptiveAire ND-2 lists 150–250 CFM/ft on a single wall hood depending on cooking-surface temperature.

Is NFPA 96 the same as the IMC hood rules?

No. NFPA 96 is a separate fire-protection standard for commercial cooking operations, and many jurisdictions adopt it alongside or instead of IMC provisions. This chart cites only IMC text we verified. Check your local code for NFPA 96 requirements.